HomeMy WebLinkAbout021278 ORD - 11/05/1991AN ORDINANCE
AMENDING THE CODE OF ORDINANCES, SECTION 13-201,
ADMINISTRATION OF THE PLUMBING CODE, TO PROVIDE DESIGN AND
MAINTENANCE CRITERIA FOR GREASE, SAND AND OIL INTERCEPTORS.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CORPUS
CHRISTI, TEXAS:
SECTION 1. That the Code of Ordinances, is hereby amended by amending
Section 13-201, Administration of the Plumbing Code, by amending Section 102,
Organization, by deleting subsection 102.1, Building Official and Inspectors, in its entirety and
substituting therefor a new subsection 102.1, and by adding a new Subparagraph (I), Grease
Interceptor Criteria, and a new Subparagraph (m), Oil and Sand Interceptor Criteria, to
Section 104 -Local Environmental, Atmospheric, and Soil Conditions, to read as follows:
Sec. 102 --Organization.
102.1 --Building Official and Inspectors.
The Building Official is hereby designated as the person responsible for the
administration and enforcement of the Plumbing Code of the City of Corpus
Christi, and who shall have the authority hereinafter provided for the "plumbing
official," the "gas official," the "wastewater official," the "health official," and "the
administrative authority." The Building Official may delegate said authority to
assistants, inspectors and other employees of the Building Inspection
Department and other employees of the departments named herein.
(/) - GREASE INTERCEPTOR CRITERIA
(1) - DESIGN CRITERIA AND SIZING METHODS
(1.1) Grease interceptors will be sized according to the fixture unit flow rate of
each fixture discharging into the interceptor. Fixture unit flow rate shall
be 7.5 GPM per fixture unit. One, two, or three compartment sinks shall
be assigned a fixture unit value of 3.0. Dishwashing and utensil washing
machines shall be assigned a fixture unit value of 6.0. For all other
grease producing fixtures, use Table 1304.2 and select appropriate
fixture unit value.
(1.2) When total fixture count has been determined, multiply value by 7.5
GPM/FU to obtain total flow rate.
(1.3) Floor drains and hand sinks installed only for the purpose of cleanup,
and not used for direct discharge of any grease producing fixture, shall
MISC:91141
1
n w;
0212 3
not be included in the sizing calculations. Such drains shall be
connected to the grease interceptor.
(1.4) Each grease interceptor must have an approved water seal of not less
than two inches in depth, or the diameter of its outlet, whichever is
greater.
(1.5) Grease interceptors must be designed so that they will not become air -
bound if tight covers are used.
(1.6) Food waste disposers shall discharge directly into the building sewer
system without passing through a grease interceptor.
(1.7) A four inch sampling port shall be installed downstream of the confluence
of the grease interceptor discharge and the building sewer system. The
sampling port shall be installed perpendicular to the effluent lateral to
allow visual observation and sampling. The design location shall ensure
accessibility of the sampling port for monitoring activities.
(2) TYPES OF INTERCEPTORS
(2.1) Accepted Materials. Factory fabricated interceptors may be of the
following materials: cast iron, stainless steel, concrete, and other
industry approved materials.
(2.2) Factory Fabricated Interceptors. Factory fabricated grease interceptors
must be certified and labeled by the Plumbing and Drainage Institute
(PDI).
(2.2.1) Factory fabricated grease interceptors shall have a minimum flow
rate of 25 GPM and a maximum flow rate of 50 GPM.
(2.2.2) When factory fabricated interceptors are installed, flow control
devices may be installed at the drain outlet of each grease
producing fixture.
(2.3) Custom Fabricated Interceptors. After calculating the required flow rate,
the grease interceptor is to be designed with a primary compartment
having a seven (7) minute retention time, and a secondary compartment
having a five (5) minute retention time. Refer to Figure 104(1).1 for details
of construction and inlet and outlet piping arrangements.
(2.3.1) Custom fabricated concrete grease interceptors shall have a
minimum flow rate of 40 gallons per minute for each compartment.
(2.3.2) Concrete shall be a minimum of 3000 PSI concrete.
MISC:91141 2
(3) PROHIBITED USES
(3.1) Carbon steel grease interceptors are prohibited in underground
applications.
(3.2) Flow control devices shall not be used with custom fabricated concrete
interceptors.
(3.3) Water cooled grease interceptors are prohibited.
(3.4) Enzyme or other chemicals are prohibited in the system. The temporary
use of enzymes or other chemicals may be permitted if the Building
Official determines unusual circumstances exist.
(3.5) Flow control devices having adjustable or removable parts are prohibited.
(4) GREASE INTERCEPTORS NOT REQUIRED
(4.1) Grease interceptors are not required in one and two family residential
dwellings.
(5) MAINTENANCE
(5.1) Grease interceptors shall be cleaned a minimum of once a quarter.
Grease interceptors must be maintained in an efficient operating
condition by removal of accumulated grease.
(5.2) The owner, operator, or manager of a premises which has a grease
interceptor shall have records which show:
- the date that the grease interceptor is cleaned;
- the name of the company which removed the grease;
the site from which the grease was removed;
- the site at which the grease was disposed;
the signature of the owner, operator or manager of the
establishment with the grease interceptor and the signature
of the driver of the truck for the company removing the
grease with a statement that all the information provided is
true and correct.
The owner, operator, or manager of the establishment shall maintain a
file that includes, at a minimum, maintenance reports for the current
month and the previous twelve (12) month period. The records shall be
kept on the premises at all times and shall be made available for review
during normal business hours upon request by the Building Official.
MISC:91141 3
(5.3) The grease collected from a grease interceptor, and all waste cooking
oils and greases used in food preparation, shall not be discharged into
any sewer.
(5.4) The owner, operator, or manager of a premises which has a grease
interceptor shall comply with the Commercial and Industrial Waste
Disposal and Pretreatment Ordinance.
(5.5) The sampling port location shall remain accessible to City employees for
monitoring activities.
(6) ENFORCEMENT
(6.1) Failure to timely clean and keep grease interceptors clean causes or may
cause substantial interference to the publicly owned treatment works, or
may cause damage to sanitary sewer facilities or structures, or otherwise
may create an emergency condition requiring immediate corrective
action. The cleaning of the grease interceptors and the record keeping
required in conjunction therewith shall be subject to enforcement in the
same manner as for violations of the Commercial and Industrial Waste
Disposal and Pretreatment Ordinance, Sec. 55-147 Enforcement. The
City Building Official may order more frequent cleaning of grease
interceptors than once a quarter or upgrading of the grease interceptors
to code requirements.
(6.2) An undersized grease interceptor installed prior to December 1, 1991,
which does not have additional future fixtures installed, shall not be
required to be replaced in conformance with sizing standards set out
herein, provided that the interceptor does not discharge grease into the
sanitary sewer system.
(6.3) The Building Official may require any grease interceptor which discharges
grease into the sanitary sewer system to be replaced with a grease
interceptor which conforms to the sizing standards set out above.
(6.4) Any owner, operator or manager of a premises which has a grease
interceptor which discharges grease into the sanitary sewer system shall
comply with the orders of the Building Official to replace the interceptor
within six (6) months from the date the orders were issued.
(m) - OIL AND SAND INTERCEPTOR CRITERIA
(1) DESIGN CRITERIA AND SIZING METHODS
(1.1) The sizing method for custom fabricated oil and sand interceptors
assigns a flow rate of 20 GPM (gallons per minute) for the first bay and
MISC:91141 4
an additional 10 GPM for each additional bay. The tank should be
designed to have a twelve (12) minute retention time with two
compartments. The primary compartment shall be 2/3 of the total
volume and the secondary compartment shall be 1/3 of the total volume.
See Figure 104(m).1 and Figure 104(m).2 for details of construction and
piping arrangements.
(1.2) Concrete used for interceptor construction must be at least 3000 PSI.
(1.3) Oil and sand interceptors must be designed so that they will not become
air -bound if tight covers are used.
(1.4) Oil and sand interceptors shall drain into the sanitary sewer only.
(2) - MAINTENANCE
(2.1) The owner, operator, or manager of a premises which has an oil or sand
interceptor shall have records which show:
The date of the most recent cleaning of the oil or sand
interceptor.
The name of the company who cleaned the interceptor(s).
The site from which the oil or sand was removed.
The site at which the oil or sand is disposed.
The signature of the owner, operator or manager of the
establishment with the oil or sand interceptor and the
signature of the driver of the truck for the company
removing the waste with a statement that all the information
provided is true and correct.
The owner, operator, or manager of the establishment shall maintain a
file that includes, at a minimum, maintenance reports for the current
month and the previous twelve (12) month period. The records shall be
kept on the premises at all times and shall be made available for review
during normal business hours upon request by the Building Official.
(2.2) The sand, oil, and other wastes collected from the cleaning of an oil or
sand interceptor shall not be discharged into any sewer.
(2.3) Oil and sand interceptors shall be cleaned and maintained on a regular
basis so that no oil or sand is discharged into the sanitary sewer system.
Oil and sand interceptors must be maintained in an efficient operating
condition by removal of accumulated oil and sand.
SECTION 3. If for any reason any section, paragraph, subdivision, clause,
phrase, word or provision of this ordinance shall be held invalid or unconstitutional by final
MISC:91141 5
judgment of a court of competent jurisdiction, it shall not affect any other section, paragraph,
subdivision, clause, phrase, word or provision of this ordinance for it is the definite intent of
this City Council that every section, paragraph, subdivision, clause, phrase, word or provision
hereof be given full force and effect for its purpose.
SECTION 4. Publication shall be made one time in the official publication of the
City of Corpus Christi by publishing the caption stating in substance the purpose of the
ordinance, this ordinance to become effective upon such publication.
MISC:91141 6
FIGURE 104(I).1
FIGURE 104(mjb
11
FIGURE 104(m).2
That the foregoing gdinancpe was read for(the first time and passed to its second reading c
the c -Y r day of C.,(` t , 19 T } , by the following vote:
Mary Rhodes
Cezar Galindo
Leo Guerrero
Betty Jean Longoria
l Q
rceicidErj
Edward A. Martin
Joe McComb
Dr. David McNichols
Clif Moss
Mary Pat Slavik
(L.
akp
6 OADaoed
That the foregoing ord' nce vewnt�s read for tlie, second time and passed to its third reading on
this the day of d"etti ¢ , 19 7 ( , by the following vote:
Mary Rhodes
Cezar Galindo
Leo Guerrero
Betty Jean Longoria
That the
day of
Edward A. Martin
Joe McComb
Dr. David McNichols
Clif Moss
Mary Pat Slavik
(LI7
oregoing, ordinance `w read for the third time and passed finally on this the
nt L/A ) , 19"f , by the following vote:
Mary Rhodes
Cezar Galindo
Leo Guerrero
Betty Jean Longoria
a e d -
PASSED AND APPROVED, this the
ATTEST:
ilAittvve'
City Secretary
APPROVED: g DAY OF a
Edward A. Martin
Joe McComb
Dr. David McNichols
Clif Moss
Mary Pat Slavik
day of U tt..Q al oALJ , 19(1(
JAMES R. BRAY, JR., CITY ATTORNEY
By ..
044
MA OR
THE CIT
u, a Assistant City Attorney
021273
CORPUS CHRISTI
PUBLISHER'S AFFIDAVIT
State of Texas,
County of Nueces } ss:
CITY OF CORPUS CHRISTI
Ad #42129
PO #
Before me, the undersigned, a Notary Public, this day personally
came Kerri Lesmeister, who being first duly sworn, according to
law, says that she is a Business Office Secretary of the Corpus
Christi Caller -Times, a daily newspaper published at Corpus
Christi in said County and State, generally circulated in
Aransas, Bee, Brooks, Cameron, Duval, Hidalgo, Jim Hogg, Jim
Wells, Karnes, Kenedy, Kleberg, Live Oak, Nueces, Refugio, San
Patricio, Victoria, and Webb Counties, and that the publication
of NOTICE OF PASSAGE OF ORDINANCE NO. 021278. AMENDING THE CODE
which the annexed is a true copy, was published in the Corpus
Christi Caller -Times on the llth day of November 1991.
One Time(s)
$ 24.30
-f.% 4 c 2 4:-,e-c&c
Business Office Secretary
Subscribed and sworn to before me this 26th day of
November , 1991.
Uxo UL)!ivyeal
Notary Public, Nueces County, Texas
My commission expires on 4-24-93 .
atlas 1
t
AME � CODE 127.Pro
O DIN1 ' SECTION pro
iii , `. N$TRATION P
PROVIDE >"��' AND COMAIN- por
TO
TEN a TERIA FOR 01°GREASE:. AND OIL IN- to
TERC , aro
T as peo �
and bythe City
Co A 7ryaas on the W
5th of ° °. , 1991. v'
o Chaps